GIS RMU

3.3-40.5 kV

Gas Insulated Switchgear

Product parameters:

  • SF6 insulation ring main unit
  • Indoor medium voltage distribution switchgear
  • Rated voltage: 3.3kV, 6kV, 10kV, 11kV, 12.5kV, 13.8kV, 15kV, 17kV, 22kV, 24kV, 33kV, 36kV, 40.5kV.
  • Floor standing
  • Annual leakage rate ≤0.25‰ per year
  • SF6 gas pressure at 20℃ is 0.4bars(relative pressure)
  • Standard: IEC, ANSI, GB
  • UN-GM6

General

UN-GM6 is a SF6-insulated ring main unit for the secondary distribution network. UN-GM6 can be supplied in 10 different configurations suitable for most switching applications in 12/24/36 kV distribution networks. As an option, UN-GM6 can be delivered as extendable ring main unit.

Together, UN-GM6 represent a complete solution for 12/24/36 kV secondary distribution networks. UN-GM6 have identical user interfaces.

UN-GM6 is a completely sealed system with a stainless-steel tank containing all the live parts and switching functions. A sealed steel tank with constant atmospheric conditions ensures a high level of reliability as well as personnel safety and a virtually maintenance-free system.

The UN-GM6 concept offers a choice of either a switch fuse combination or circuit breaker with relay for protection of the transformer. UN-GM6 can be supplied with an integrated remote control and monitoring unit.

UN-GM6 is a SF6-insulated, extendable compact switchgear system for secondary distribution. The switchgear has a unique flexibility due to its extendability and the possible combination of fully modular and semi modular configurations.

UN-GM6 also has non-extendable cabinet, which save cost on external busbar and smaller size.

When combined with UN-GM6, which is UNISUN standard ring main unit, they represent a complete solution for 12/24/36 kV distribution networks.

 

Standard
All UNISUN transformers are in conformity with IEC standards, Transformers in conformity with specific country standards can also be supplied. (IEEE, GB)

Outer assembly

Technical date of C cabinet

Rated voltage

kV

12

17,5

24

36

Power frequency withstand voltage

kV

281) 

38

50

70

Impulse withstand voltage

kV

95

95

125

170

Rated normal current

A

630

630

630

630

Breaking capacities:

 

 

 

 

 

– active load

A

630

630

630

630

– closed loop

A

650

650

650

630

– off load cable charging

A

140

140

140

20

– earth-fault

A

205

160

160

60

– earth-fault cable charging

A

117

91

91

35

Making capacity

kA

62.5

52.5

52.5

50

Short time current 3 sec.

kA

25

21

21

20

Number of mechanical operations

1000 close / open manual

Earthing switch

Rated voltage

kV

12

17,5

24

36

Power frequency withstand voltage

kV

281) 

38

50

70

Impulse withstand voltage

kV

95

95

125

170

Making capacity

kA

62.5

50

50

50

Short time current 3 sec.

kA

25

21

21

20

Number of mechanical operations

1000 close / open manual

1) Available with 42kV power frequency withstand voltage 

 

 

Technical date of F cabinet

Switch disconnector

Rated voltage

kV

12

17,5

24

36

Power frequency withstand voltage

kV

282) 

38

50

70

Impulse withstand voltage

kV

95

95

125

170

Rated normal current

A

200

200

200

630

Breaking capacities:

 

 

 

 

 

– off load transformer

A

20

20

20

630

Making capacity

kA

1)

1)

1)

50

Number of mechanical operations

1000 close / open manual

Earthing switch

Rated voltage

kV

12

17,5

24

36

Power frequency withstand voltage

kV

282) 

38

50

70

Impulse withstand voltage

kV

95

95

125

170

Making capacity

kA

12.5

12.5

12.5

50

Short time current 1 sec.

kA

5

5

5

20

Number of mechanical operations

1000 close / open manual

1)         Limited by high voltage fuse-links

2)         Available with 42kV power frequency withstand voltage 

 

Technical date of V cabinet

Switch disconnector

Rated voltage

kV

12

17,5

24

36

Power frequency withstand voltage

kV

281) 

38

50

70

Impulse withstand voltage

kV

95

95

125

170

Rated normal current

A

200/6302) 

Breaking capacities:

 

 

 

 

 

– short-circuit breaking current

kA

21

16

16

20

Making capacity

kA

52.5 

40

40

50

Short time current 3 sec. 3) 

kA

21

16

16

20

Number of mechanical operations

2000 close / open manual

Operation sequence

O – 3min – CO – 3min – CO

Earthing switch downstream

Rated voltage

kV

12

17,5

24

36

Power frequency withstand voltage

kV

281) 

38

50

70

Impulse withstand voltage

kV

95

95

125

170

Making capacity

kA

52.5 

40

40

50

Short time current 3 sec.

kA

21

16

16

20

Number of mechanical operations

1000 close / open manual

1)         Available with 42kV power frequency withstand voltage

2)         Depend on type of used bushing

 

3)         Interface A – 12,5kA/1s, interface B – 16kA/1s 

 

Waiting for your enquiry!

Why Buy From Us

Professional Quality Guarantee
Easy and Affordable Payments
Best Product Guarantee

Our Production

The products are designed in strict accordance with IEC or ANSI standards, and the manufacturing steps meet the technological requirements 

Wiring design

Standardized circuit design, high purity copper bar is used for primary circuit, and the design meets the current requirements of the project. Standard copper wire is available for the secondary circuit, and the circuit design is optimized according to the requirements of the project.

Production testing

Comprehensive production inspection, in accordance with the premise of electrical performance, to ensure that each electrical component can working efficiently.  